16MWH-8MW-11KV Solution

16MWH-8MW-11KV Solution

Solution

16MWH-8MW-11KV Solution

The project consists of four 4.179MWH energy storage battery compartments and two 4MW power conversion system cabins. Each battery compartment is equipped with BMS, fire suppression, HVAC thermal management and auxiliary power distribution.

Request Solution

Project Overview

The project consists of four 4.179MWH energy storage battery compartments and two 4MW power conversion system cabins. Each battery compartment is equipped with BMS, fire suppression, HVAC thermal management and auxiliary power distribution.

Battery Compartment Specifications and Parameters

Product Model TY-YL-4019KWH
Configuration 416s10p
Rated Energy 4019kWh
Rated Voltage 1331.2V
Operating Voltage Range 1040~1500V
Dimension 6058mm × 2438mm × 2896mm
Mass ~37500kg
Rated charge power 0.5P (2090kW)
Rated discharge power 0.5P (2090kW)
Operating ambient temp -30~55℃
Cooling and heating type Liquid cooling / heating
Communication agreement CAN, RS485, TCP/IP

Boost Compartment Specifications and Parameters

Maximum DC Voltage 1500V
Maximum DC Current 5612A
Battery Pack Voltage Range 1000V-1500V
Number of Connectable Battery Packs 4
Rated AC Power 5000KW
Rated Grid Voltage 10KV-35KV
Rated Grid Frequency 50/60Hz
THD at Rated Power <3
Adjustable Power Factor Range -1~+1
Maximum System Efficiency 98%
Ingress Protection (IP) Rating IP65
Operating Ambient Temperature -40℃~+60℃
Communication Interface RS485/CAN/Ethernet

Project Images

Battery compartment, wiring, inverter, boost compartment and circuit diagrams.

16MWH-8MW-11KV Solution

16MWH-8MW-11KV Solution

Project Image

Project Image

Battery Compartment

Battery Compartment

Boost Compartment Images

Boost Compartment Images

Circuit Block Diagram

Circuit Block Diagram